RZR-Mikro
Application
RZR®-Mikro device ensures continuity of power supply in networks for the buildings of public usage, apartment houses and industry premises. The device is manufactured in versions for controlling two, three, four or five switches and works in the following arrangements:
- two sources of power supply
- three sources of power supply
- one source of power supply and a generator
- two sources of power supply and a generator
- one section of a switchboard
- two sections of a switchboard
- three sections of a switchboard
- four sections of power supply
- combinations of the above elements
Symbols of the device models, selection of arrangements and algorithms of switches are presented in configuration table.
The device realises the following connections:
- SZR – automatic connection after the loss of voltage,
- APZ – automatic switch of power after return of voltage,
- AZZ – automatic turning on of power supply after turning the device on.
Characteristics
- Manufactured using a modern RISC microprocessor.
- Small dimensions.
- Comfortable and simple operation.
- Low power consumption.
- High resistance to interferences in input/output circuits.
- Possibility of:
- direct control of the commuting elements (switches, contactors),
- setting the parameters,
- changing the operation configuration,
- monitoring the switchboard condition (switches and voltages) on an LCD display,
- external locking of the device using an external contactor,
- internal locking of the device set in the operation configuration,
- custom manufacture of the device according to individual needs of the customer.
Uproszczony schemat rozdzielni
Panel operatorski SZR
Operation
RZR®-Mikro device controls the presence of all input voltages and the position of the controlled switches. Depending on the position of switches and the presence of voltage, the device controls the coils of the switches in order to arrive at the condition presented in the table of switches. In case of power supply from a UPS, after the loss of voltage, the device switches off all switches (cycle with the possibility of locking). In the cycle of automatic return to the basic power supply APZ (return cycle), the device works after the occurrence of voltage.
Construction
The device is placed in a metal housing suitable for DIN rail assembly.
On the front plate of the device there are:
- LCD display,
- signalling the presence of voltage powering the device,
- signalling of an external lock,
- four momentary switches for changing the display on LCD panel, changing the parameters and settings of the device.
In the upper and lower parts of the housing there are connectors for coupling the device with the controlled system. The following main elements of the device are located inside the housing:
- power supply,
- output relay,
- separator circuits,
- LCD panel,
- front plate block(keyboard and light signals)
- microprocessor steering and measurement circuit.
Dane techniczne
Podstawowe dane techniczne |
|
Znamionowe napięcie pomiarowe trójfazowe Un |
AC 400V 50Hz |
Znamionowe napięcie zasilania Uz |
AC 230 V + 10%, - 20% |
Napięcie kontrolowanych faz |
180 V AC 10% |
Zakres nastawienia czasu opóźnienia rozruchu
|
.
|
Czas trwania impulsów wyjściowych do sterowania wyłączników |
0,5 s |
Uchyb członów czasowych |
≤ 1 % |
Klasa członów czasowych ze względu na rozrzut |
1 |
Uchyb dodatkowy od wpływu zmian napięcia zasilającego i temperatury |
± 1 % |
Zakres temperatury pracy |
(-5 ÷ +55) °C |
Dopuszczalna wilgotność względna |
90% (bez kondensacji) |
Obciążalność zestyków: |
|
Znamionowy pobór mocy |
≤ 10 W |
Trwałość łączeniowa przekaźników wyjściowych |
> 0,6 x 105 |
Wymiary |
(250 x 105 x 73) mm |
Waga |
ok 1,0 kg |
Stopień ochrony |
IP 40 |
Komunikacja |
|